From the Turbine to the Controller
12V & 24V System Cable Length – 2 Cores |
Rutland 504 |
Rutland 914 |
Rutland FM910-4 |
|||
mm² | AWG | mm² | AWG | mm² | AWG | |
0-20 m | 2.5 | 14 | 1.5 | 16 | 2.5 | 14 |
20-30 m | 4 | 12 | 2.5 | 14 | 4 | 12 |
30-40 m | 6 | 10 | 4 | 12 | 6 | 10 |
40-50 m | 10 | 8 | 6 | 10 | 10 | 8 |
System Cable Length – 3 Equal Cores |
Rutland 1200 12V |
Rutland 1200 24V |
||
mm² | AWG | mm² | AWG | |
0-5 m | 4 | 12 | 4 | 12 |
5-10 m | 4 | 12 | 4 | 12 |
10-20 m | 6 | 10 | 4 | 12 |
20-30 m | 10 | 8 | 4 | 12 |
30-40 m | 16 | 6 | 4 | 12 |
50-75m | 6 | 10 | ||
75-100m | 10 | 8 |
12 & 24V System Cable Length – 3 Equal Cores |
Rutland FM1803 |
|
mm² | AWG | |
0-5 m | 1.5 | 16 |
10-20 m | 1.5 | 16 |
20-30 m | 1.5 | 16 |
30-40 m | 1.5 | 16 |
40-50 m | 1.5 | 16 |
50-100 m | 2.5 | 14 |
From the Controller to the Battery
Cable Length | Rutland 504
≤ 20A |
Rutland 914
≤ 30A |
Rutland 1200
≤ 55A |
Rutland FM910-4
≤ 30A |
Rutland FM1803
≤ 55A |
|||||
mm² | AWG | mm² | AWG | mm² | AWG | mm² | AWG | mm² | AWG | |
1.5 m | 4 | 12 | 4 | 12 | 16 | 6 | 4 | 12 | 16 | 6 |
From the PV Panel to Regulator
12V | Peak PV Current Rating | |||||||||
Cable Length | 5A | 10A | 20A | |||||||
mm² | AWG | mm² | AWG | mm² | AWG | |||||
2m | 1.5 | 16 | 1.5 | 16 | 2.5 | 14 | ||||
5m | 1.5 | 16 | 4 | 12 | 6 | 10 | ||||
10m | 4 | 12 | 6 | 10 | 16 | 6 |
24V | Peak PV Current Rating | |||||||||
Cable Length | 5A | 10A | 20A | |||||||
mm² | AWG | mm² | AWG | mm² | AWG | |||||
2m | 1.5 | 16 | 1.5 | 16 | 1.5 | 16 | ||||
5m | 1.5 | 16 | 4 | 12 | 4 | 12 | ||||
10m | 2.5 | 14 | 6 | 10 | 10 | 8 |